Three-phase ACCLs

M32F

M32F:

  • Ultra compact 3 phase ACCLs with interlocked contactor design.
  • Just 101mm wide (less than 6 MCBs wide)
  • Pure white FR polycarbonate enclosure with fine, custom-made terminals for better operation and aesthetics.
  • DG Limits can be set at factory on order, and can also be set on-site.
Rated Loads32A, FP (EB); 32A, FP(DG)
Suited forPower + Lighting loads
Dimensions (WxHxD)101 x 150 x 124 mm
Switching deviceContactor
No. of Poles4 (3P+N)
Rated Voltage415V (L-L) / 240V (P-N), 50 Hz.
Mains Rated Current (AC1)32A
Mains Rated Current (AC3)18A
Generator Trip Range (AC1)1-32A
Starting Voltage Range (Mains, P-N)180-300V
Operating Voltage Range (Mains, P-N)180-300V (310-520V L-L)
Operating Voltage Range (Gen, P-N)170-250V
Generator output on-delay4-10 seconds, randomized on boot-up
Transfer Time1 second
Self-resetting Time (after tripping)4-10 seconds
Under/over-voltage Protection (Mains)Optional
Under/over-voltage Protection (Gen)Yes, 170-270V
Utilisation CategoryAC1 / AC7a / AC7b
Electrical Endurance (Operations)60,000
Enclosure MaterialPolycarbonate (Fire-retardant)
Mounting TypeDIN (35mm)
Terminal Capacity16 mm2
Dimensions in mm (W x H x D)101 x 150 x 124
Weight1.1 KG
ConformityIEC 60947-4 / IEC 60947-6-1
Protection ClassIP20
Ambient Temperature-10° – 65°C
Rated Insulation Voltage1.1 kV
Load Switching DeviceInterlocked Dual Contactor
Short-circuit withstand capacity6kA
Optional on-demand featuresGenerator output lock-out; On-site reconfiguration

 

 

M45F

M45F:

  • Time-tested 3 phase ACCLs with interlocked contactor design for complete safety and seamless operation.
  • Superb performance track-record.
  • Pure white FR polycarbonate enclosure with fine, custom-made terminals for better operation and aesthetics.
Rated Loads45A, FP (EB); 45A, FP (DG)
Suited forLighting + power loads.
Dimensions (WxHxD)122 x 157 x 148 mm
Switching deviceContactor



No. of Poles4 (3P+N)
Rated Voltage415V (L-L) / 240V (P-N), 50 Hz.
Mains Rated Current (AC1)45A
Mains Rated Current (AC3)25A
Generator Trip Range (AC1)1-45A
Starting Voltage Range (Mains, P-N)180-300V
Operating Voltage Range (Mains, P-N)180-300V (310-520V L-L)
Operating Voltage Range (Gen, P-N)170-250V
Generator output on-delay4-10 seconds, randomized on boot-up
Transfer Time1 second
Self-resetting Time (after tripping)4-10 seconds
Under/over-voltage Protection (Mains)Optional
Under/over-voltage Protection (Gen)Yes, 170-270V
Utilisation CategoryAC1 / AC7a / AC7b
Electrical Endurance (Operations)60,000
Enclosure MaterialPolycarbonate (Fire-retardant)
Mounting TypeDIN (35mm / 75 mm)
Terminal Capacity16 mm2
Dimensions in mm (W x H x D)122 x 157 x 148
Weight1.54 KG
ConformityIEC 60947-4 / IEC 60947-6-1
Protection ClassIP20
Ambient Temperature-10° – 65°C
Rated Insulation Voltage1.1 kV
Load Switching DeviceInterlocked Dual Contactor
Short-circuit withstand capacity6kA
Optional on-demand featuresGenerator output lock-out; On-site reconfiguration
 

M63FS

M63FS:

  • All-new 63A three-phase ACCL in the same compact size as M45F!
  • Great for projects where panel size and cost are constrained.
  • Pure white FR polycarbonate enclosure with fine, custom-made terminals for better operation and aesthetics.
Rated Loads63A, FP (EB); 63A, FP (DG)
Suited forLighting + power loads.
Dimensions (WxHxD)122 x 157 x 148 mm
Switching deviceContactor



No. of Poles4 (3P+N)
Rated Voltage415V (L-L) / 240V (P-N), 50 Hz.
Mains Rated Current (AC1)63A
Mains Rated Current (AC3)
Generator Trip Range (AC1)1-63A
Starting Voltage Range (Mains, P-N)180-300V
Operating Voltage Range (Mains, P-N)180-300V (310-520V L-L)
Operating Voltage Range (Gen, P-N)170-250V
Generator output on-delay4-10 seconds, randomized on boot-up
Transfer Time1 second
Self-resetting Time (after tripping)4-10 seconds
Under/over-voltage Protection (Mains)Optional
Under/over-voltage Protection (Gen)Yes, 170-270V
Utilisation CategoryAC1 / AC7a / AC7b
Electrical Endurance (Operations)60,000
Enclosure MaterialPolycarbonate (Fire-retardant)
Mounting TypeDIN (35mm / 75 mm)
Terminal Capacity16 mm2
Dimensions in mm (W x H x D)122 x 157 x 148
Weight1.6 KG
ConformityIEC 60947-4 / IEC 60947-6-1
Protection ClassIP20
Ambient Temperature-10° – 65°C
Rated Insulation Voltage1.1 kV
Load Switching DeviceInterlocked Dual Contactor
Short-circuit withstand capacity6kA
Optional on-demand featuresGenerator output lock-out; On-site reconfiguration
 

M63F | M70F

M63F / M70F:

  • High current capacity ACCLs for luxury residential and commercial projects, using heavy-duty contactors for supreme robustness and reliability.
  • Fire-retardant polycarbonate body – unique in its class!
  • Option for both DIN-channel and surface mounting.
  • Double-screw terminals for secure connections.
Rated Loads (EB & DG)M63F: 63A FP;

 

M70F: 70A, FP

Suited forLighting + power loads.
Dimensions (WxHxD)185 x 220 x 180 mm
Switching deviceContactor



No. of Poles4 (3P+N)
Rated Voltage415V (L-L) / 240V (P-N), 50 Hz.
Mains Rated Current (AC1)M63F: 63A; M70F: 70A
Mains Rated Current (AC3)M63F: 40A; M70F: 50A
Generator Trip Range (AC1)M63F: 1-63A; M70F: 1-70A
Starting Voltage Range (Mains, P-N)180-300V
Operating Voltage Range (Mains, P-N)180-300V (310-520V L-L)
Operating Voltage Range (Gen, P-N)170-250V
Generator output on-delay4-10 seconds, randomized on boot-up
Transfer Time1 second
Self-resetting Time (after tripping)4-10 seconds
Under/over-voltage Protection (Mains)Optional
Under/over-voltage Protection (Gen)Yes, 170-270V
Utilisation CategoryAC1 / AC7a / AC7b
Electrical Endurance (Operations)60,000
Enclosure MaterialPolycarbonate (Fire-retardant)
Mounting TypeDIN (35mm / 75 mm) / Surface
Terminal Capacity35 mm2
Dimensions in mm (W x H x D)185 x 220 x 180
Weight3.6 KG
ConformityIEC 60947-4 / IEC 60947-6-1
Protection ClassIP20
Ambient Temperature-10° – 65°C
Rated Insulation Voltage1.1 kV
Load Switching DeviceInterlocked Dual Contactor
Short-circuit withstand capacity6kA
Optional on-demand featuresGenerator output lock-out; On-site reconfiguration

ATS 80

ATS 80:

In addition to standard 3 phase ACCL functionality, ATS models offer features such as continuous monitoring of all three-phase voltages and giving priority to DG in case any of the EB phases are unhealthy, acting as a mains single-phasing preventer (when DG is on). The ATS 80 comes in the same FRPC body as M70F, whereas the ATS 125 is built in a robust sheet-metal enclosure

Rated Loads80A/125A
Suited forLighting + power loads.
Dimensions (WxHxD)185 x 220 x 180 mm
Switching deviceContactor



No. of Poles4 (3P+N)
Rated Voltage415V (L-L) / 240V (P-N), 50 Hz.
Mains Rated Current (AC1)80A
Mains Rated Current (AC3)65A
Generator Trip Range (AC1)1-80A
Starting Voltage Range (Mains, P-N)180-300V
Operating Voltage Range (Mains, P-N)180-300V (310-520V L-L)
Operating Voltage Range (Gen, P-N)170-250V
Generator output on-delay4-10 seconds, randomized on boot-up
Transfer Time1 second
Self-resetting Time (after tripping)4-10 seconds
Under/over-voltage Protection (Mains)Optional
Under/over-voltage Protection (Gen)Yes, 170-270V
Utilisation CategoryAC1 / AC7a / AC7b
Electrical Endurance (Operations)60,000
Enclosure MaterialPolycarbonate (Fire-retardant)
Mounting TypeDIN (35mm / 75 mm) / Surface
Terminal Capacity35 mm2
Dimensions in mm (W x H x D)185 x 220 x 180
Weight3.8 KG
ConformityIEC 60947-4 / IEC 60947-6-1
Protection ClassIP20
Ambient Temperature-10° – 65°C
Rated Insulation Voltage1.1 kV
Load Switching DeviceInterlocked Dual Contactor
Short-circuit withstand capacity6kA
Optional on-demand featuresGenerator output lock-out; On-site reconfiguration

ATS 125

ATS 125:

In addition to standard 3 phase ACCL functionality, ATS models offer features such as continuous monitoring of all three-phase voltages and giving priority to DG in case any of the EB phases are unhealthy, acting as a mains single-phasing preventer (when DG is on). ATS 125 is built in a robust sheet-metal enclosure.

Rated Loads125A, FP
Suited forLighting + power loads.
Dimensions (WxHxD)265 x 250 x 165 mm
Switching deviceContactor



No. of Poles4 (3P+N)
Rated Voltage415V (L-L) / 240V (P-N), 50 Hz.
Mains Rated Current (AC1)125A
Mains Rated Current (AC3)95A
Generator Trip Range (AC1)1-125A
Starting Voltage Range (Mains, P-N)180-300V
Operating Voltage Range (Mains, P-N)180-300V (310-520V L-L)
Operating Voltage Range (Gen, P-N)170-250V
Generator output on-delay4-10 seconds, randomized on boot-up
Transfer Time1 second
Self-resetting Time (after tripping)4-10 seconds
Under/over-voltage Protection (Mains)Optional
Under/over-voltage Protection (Gen)Yes, 170-270V
Utilisation CategoryAC1 / AC7a / AC7b
Electrical Endurance (Operations)60,000
Enclosure MaterialSheet-metal
Mounting TypeSurface
Terminal Capacity35 mm2
Dimensions in mm (W x H x D)215 x 265 x 185
Weight6.5 KG
ConformityIEC 60947-4 / IEC 60947-6-1
Protection ClassIP20
Ambient Temperature-10° – 65°C
Rated Insulation Voltage1.1 kV
Load Switching DeviceInterlocked Dual Contactor
Short-circuit withstand capacity6kA